ECO-I VRF Systems - Heat Pump Outdoor Unit Discontinued

WU-168ME1U9

Product details

  • ECO-i VRF Systems - Heat Pump Outdoor Unit
  • Capacity Cooling: 164,000
  • Capacity Heating: 184,000
  • Includes (1) U-72ME1U9 and (1) U-96ME1U9

Specification Description
Capacity Control Range (%) 6 - 100
Coil Face Area (sq ft) 29.5
Capacity Cooling (BTU/H) 164,000
Cooling Mode: Indoor Conditions (°F WB/°F DB) 80/67
Cooling Mode: Level Difference (ft) 0
Cooling Mode: Outdoor Conditions (°F DB) 95
Cooling Mode: Pipe Length (ft) 25
Crankcase Heaters (W) 25+25+32
External Static Pressure .0/.24
Fan Motor Output (KW) 0.7
Fan Type/ Quantity 1 Propeller
Capacity Heating (BTU/H) 184,000
Heating Mode: Indoor Conditions (°F DB) 70
Heating Mode: Level Difference (ft) 0
Heating Mode: Outdoor Conditions (°F DB/°F WB) 47/43
Heating Mode: Pipe Length (ft) 25
High Pressure Switch/Overcurrent (CT Method) Yes
Max. Overcurrent Protection (MOCP) (A) 85
Minimum Circuits Amps (MCA) (A) 60
Nominal Operating Range: Cooling (°F DB) 14 to 113
Nominal Operating Range: Heating (°F WB) -4 to 59
Outdoor Capacity Up to 168000 BTU
Outdoor Capacity (Tons) 14 Tons
Outdoor Unit 2-Way Heat Pump
Power Input - Cooling (W) 12.97
Power Input - Heating (W) 14.39
Power Supply (V, Phase, Hz) 208 / 230V 60Hz
Number of Rows 4
Salt Protection No
Type Heat Pump Outdoor Units
Type/ Quantity 2 Inverter Driven Twin Rotary and Fixed Speed Scroll
Unit ECOi VRF System
Weight 1,267